EPA 200 Process Control Device || ATEK || Made in Türkiye

Process and temperature measurement at the same time
RS-232, RS-485, USB or CANopen communication options
Analog output options
2 relay outputs (optional 3), adjustable for different functions
24 VAC/DC or 85-265 VAC supply options
Two lines 5 digits display

Universal process control device; RS-232, RS-485, USB or CANopen option; 3.5 kHz high sampling rate

Display Input Options Supply Voltage Datasheet
Dual line, 5 digits Potentiometer, 0.5-4.5 V, 0-5 V, 0-10 V, 4-20 mA, 0-20 mA, 3.33 mV/V, 2mV/V, 2.5mV/V Ratiometric, Thermocouple, RTD, CANopen 24 VAC/DC 50/60 Hz 85-265 VAC 50/60 Hz
  • Process and temperature measurement at the same time
  • Two lines display;
  • The first line shows the analog process value from the sensor and the second line shows the temperature information from the thermocouple.
  • PT100, PT1000 or Thermocouples can be connected
  • Thermocouple type K, J, N, R, S, T, E and B can be selected from menu
  • Temperature can be shown as °C, °K and °F .
  • Load Cell connection can be made
  • RS-232, RS-485, USB or CANopen options
  • 2 relay outputs (optional 3), adjustable for different functions
  • High refresh rate: 3.5 kHz
  • Analogue signals (0-10 V, 4-20 mA, 0-20 mA Potantiometric) can be converted to CANopen signals.
  • CANopen signals can be converted to analogue signals (0-10 V, 4-20 mA,  0-20 mA) 
  • Reversible analogue  output (10-0 V, 20-0 mA)
  • Fast and multiple parameter configuration via USB
  • Easy and user friendly interface
  • Tare function
  • Menu hiding or password protection
Brand

Atek

Supply Voltage

24 VAC/DC 50/60 Hz
85-265 VAC 50/60 Hz

Power Consumption

9 VA / 2,7 Watt Maximum

Sensor Supply Voltage

Pot: 5 VDC
mV/V: 10 VDC
0-10V: 24 VDC
0-5V: 5 VDC
0,5-4,5V: 5 VDC
4-20 mA: 24 VDC
CANopen: 24 VDC

Max. Sensor Supply Current

100 mA

Refresh Rate

3.5 kHz

Resolution

16 bit

Analogue Inputs

Potentiometer, 0.5-4.5 V, 0-5 V, 0-10 V, 4-20 mA, 0-20 mA, 3,33 mV/V, 2 mV/V, 2.5 mV/V, Thermocouples, RTD

Relay Outputs

2 x 250 VAC 3A (Resistive Load) Relay (optional 3 relays)

Serial Communication (Optional)

RS-232, RS-485, USB, CANopen

Analogue Outputs (Optional)

0-10 V, 0-5 V, 0.5- 4.5 V, 4-20 mA, 0-20 mA

Electrical Connection

2,5 mm² connection terminal

Operating Temperature

0 and 50 °C

Protection Class

IP60 Front Panel, IP20 Back Panel

  • Instantaneous display of output of any measuring device with Potentiometric, Voltage, Current or CANopen output
  • Where your automation solutions require sensor output relay output